Technical Specifications
Dimensions: 4.40 in x 6.90 in x 1.50 in (111 mm x 175 mm x 38 mm)
Environmental considerations:
- Relative humidity: 5% to 93% at +32°C (+90°F)
- Temperature (operating): 0°C to +49°C (+32°F to +120°F)
- Operational use: Indoor use only
Power requirements:
- Standby battery current: Battery input: B465: Idle 150 mA; Alarm 230 mA
- 24 VDC input current: 24 VDC input: B465: Idle 120 mA; Alarm 160 mA
Wiring:
- Terminal wire size: 12 AWG to 22 AWG (2.0 mm to 0.65 mm)
- Transformer secondary wiring length: 15 m (50 ft) maximum unshielded wire
- Control panel phone line wiring: 100 Ω loop resistance, maximum unshielded wire
- Input loop wiring: 100 Ω loop resistance, maximum unshielded wire
- Ethernet wiring: 100 m (328 ft) maximum